Support

9 Support Entries

Possible cause:

  • Defective print.

Corrective measure:

  • Replace the small print for eject station.

Possible cause:

  • The power percentage is too high! If the power percentage rises up to 96%, the LED is flashing. In this case the pacemaker does not have enough spare power to regulate the current properly.

Corrective:

  • To solve the problem, reduce current/frequency value or use a higher transformer step.

Cause:

The actual value of the weld power limiter increases with the heating of the machine.


Corretive:

Readjust the weld power limiter, to a higher value. Observe the “Max” value from a “cold “ start to a “warm up” machine during production. See also note below.


NOTE:

Power limit to activate the weld guard (stitch welding). Normally 5 – 10 % more than the actual “Max” value during production.
0 = Weld Power Limiter Off !

 

Problem:
The display shows the set current value, but the duty cycle is very low or 0%!

Possible cause:

  • Short circuit in the welding transformer!

 

DO NOT ATTEMPT TO SWITCH “ON” THE CURRENT ANYMORE!
Further attempts to switch on the current, can destroy or damage the semiconductors (IGBT) in the Pacemaker!

Using a handpanel:
When you start up your Pacemaker, the software version will be displayed during the boot process.

Alternatively the information will we displayed, when you press the key “down” several times until you get to “Info Version”: e.g. 5.27

Using a CM16 welder you will also find the info by pressing the key “down”, since the display is the same as the handpanel of a PM.


Using a X1 welder:

Tip on the *eye” icon and the Pacemaker software version is displayed on the bottom line.

Using X8 welder:

Tip on the “eye” icon and then on a second “eye” icon to get to software version info on the bottom line – check also your manual book 1 – chapter 4.6. how to find the info.

Scroll down in the display menu until you reach the temperature display. Observe, if after crossing the switching threshold, the temperature doesn’t change, that the solenoid valve is blocked (when the 2nd thresholds are reached the message “over- or undertemperature” will be displayed).

NOTE: The error message “Ths too low (Ths = Temperature Heatsink)” might be an indication for a contaminated valve.

The Pacemaker has the following options to connect the output of the weld power limiter to other systems/controls (i.e. can rejection control):

  1. E-Relay
    E-Relay of Pacemaker does stop the welder if weld power limiter is active. To connect, use the clamp No. 45, 46 and 47 (potential free relay contact 47=>com, 46=>nc, 45=>no).
    To use this function, the parameter “Wld fault” in the Pacemaker settings has to be set to “E-Relay”. If weld power limiter is activated, the E-relay do switch on, welder stop and must be reset on the Pacemaker display before the welder can be restartet. Of course the operator has to check the last welded cans to make sure that no unwelded cans go to the downline.
  2. +Tol output (Clamp 35/36, 35=>0V, 36=>24Vdc)
    This output is switching on if the weld power limiter is active and can be used also to activate an ejector or other function. The next can will be welded normally and +Tol output will switch off automatically. If you want to use that output, you can change the parameter “Wld fault” to “nothing”. In this case, the E-relay will not be activated and the welder can run continuously without to stop if the weld power limiter detect a can. Of course you need an additional logic for the eject timing and eject the right can.
  3. +CR output (Clamp 39/40, 39=>0V, 40=>24Vdc)
    This output will be activated if the weld power limiter is active according to the parameter “WLD fault”. You can choose different settings like “CR39/40”, “CR 50ms”…
    Example: CR 50ms => Pulse of 50ms on CR output if weld power limiter detect a bad can.
  4. Can Man eject unit
    With this option it is possible to eject cans and also to eject the first and last can of a series. Please contact Can Man for an offer.Attention!!! +Tol and +CR output is supplied by the internal 24Vdc of the Pacemaker electronic board. This output is not potential free!!! Use a small 24Vdc relay to connect the signal with other systems/controls.The settings of beginning and end of can (T1/T2 or IT/ET) must be set correctly, also if you don’t use the IRED function. With this timing, the weld power do switch on the current for the next can after a stop in case of contamination (overlacquering).Code to enter the system setup: down, right, left, left, up, left, right, right

If you have connect the control panel and you can see only strange signs in the display, the connecting speed can be wrong. The Pacemaker control panel can run in two modes.


19200 baud

Control panel standard is 19200 baud (Used for connecting between control panel and PLC )

9600 baud

9600 baud (Used only for connecting between PLC and Pacemaker)

 

How you can change to 9600 baud:

Switch off the Pacemaker (Main switch off)

Press the “MENU” button while starting the panel.  

Now the control panel runs with 9600 Baud Can Man machines with PLC.

 

How you can change to 19200 baud:

Switch off the Pacemaker (Main switch off)

Press the “RESET” button while starting the panel. 

Now the control panel runs with 19200 baud
Control panel and PLC.

Possible Cause (CM16 / S, X8):

  1. Check air supply for the cylinder.
  2. Eject cylinder must push the canbodies inthe center, the can must move verticallyaway from eject cylinder.
  3. Second light barrier is always ON.Sensor dirty or bad adjustment.
    LED on light barrier must be ON without can, OFF if a can is detected.
  4. Control wiring of first and second light barrier according electrical diagram.
  5. Make sure the faulty can is really ejected, means does not touch the edge of the bin and jumps back.
    => Use a fixed channel underneath the eject station, instead of a mobile bin!

Adjustment of the light barrier distance to eject cylinder might be wrong.

Wrong adjustment of the transport belt speed.

NOTE:
The ejected can should whether touch the can before nor the following.

Eject pulse cylinder has to fit to production speed:

Recommendation: 150-200msfor<100cpm 100-150msfor100-200cpm

80-100msfor200-400cpm

Place a canbody between the second light barrier and check the LED „LD3“ on the eject print (inside the Pacemaker).
Must be „ON“.

The autoreset needs to be “OFF”. Therefore the can memory will not be reset automatically.

Check, if your hardware parameters are set correctly, according to one of the three layouts.
=> See layouts below!


Click here for more

 

Possible Cause (Pacemaker):

  1. Check air supply for the cylinder.
  2. Second light barrier is always ON.
    Sensor dirty or bad adjustment.
    LED on light barrier must be ON without can, OFF if a can is detected.
  3. Adjustment of the light barrier distance to eject cylinder might be wrong.

  4. Wrong adjustment of the transport belt speed.
All Can Man content is now also available on the Soudronic Group website.
Where do you want to continue your journey?
All Can Man content is now also available on the Soudronic Group website.
Where do you want to continue your journey?