Problem:

Circuit breaker Q5 trips when the machine is switched on or during production.

Possible Causes or Resolutions:

  • Measure voltages at all phases, even under load. It is possible that one phase did drop down, and this triggered the circuit breaker.
  • Measure the current of each phase with a current clamp after Q5. If the measured value is below the value of the circuit breaker and Q5 still keeps tripping, the circuit breaker may be defective. Replace it.
  • Maybe the parameter “Low bat voltage” (coming from Pacemaker) is set too low: That means that the contactor in the Pacemaker closes too early with a precharge voltage that is too low and therefore Q5 trips. To check this, please open a ticket to contact CanMan.

Reason for error message:

  • The Pacemaker™  capacitor bank voltage is to low.

 

Possible causes:

  • Supply voltage mains drop down. Please check all phases even when the machine is running. Does a phase drop down?
  • Check complete wiring, Are all clamps tightened?
  • Check the 24Vdc supply terminals 17/18 on Pacemaker board. This 24Vdc are supplied by the welding machine and has to be always on. If the 24Vdc is missing, the precharging of capacitors works, but the main contactor will not switch on => Ubatt Error

 

 

  • Check the 24Vdc output terminals 41/42. After precharging is complete, 24DC should be applied here to close the main contactor. Possibly the small print relay on the electronics board is defective.

 

Problem:

Machine stops and message „Pacemaker: Profibus communication error“ is displayed.

Possible Causes & Resolutions:

  • Cooling water valve: Wrong type of valve or plug without protective circuit (suppressor). The voltage peaks can cause interferences in the Pacemaker electronics. Always use the original plug and valve type.
  • Profibus plug: On the plug of first and last client of profibus system the termination resistant must be set to ON. Otherwise interference may occur.
  • Profibus cables: Check the position of the cables in the control unit. If they are close to contactors, high voltage peaks can create interferences.

An overvoltage suppressor (or surge suppressor) is an appliance designed to protect electrical devices from voltage spikes. A surge suppressor attempts to regulate the voltage supplied to an electric device by either blocking or by shorting to ground voltages above a safe threshold.

These surge suppressors are built in to the latest Pacemaker models and machine controls (from 2009).

Check, if one or more modules of the surge suppressors are red/defect. Replace the red modules.

Attention!!!

Do not bridge the signalling contacts and run the machine with defective red modules because they no longer protect the system from voltage peaks!!!
If the modules are defective, check the main supply. Measure and check all voltages between the phases and all phases to earth before exchange the modules and restart the machine.

  1. Switch off the main switch Q1 of the machine.
  2. Wait around 10min before you do anything on the wiring of the pacemaker! The capacitors need that time to discharge!!!
  3. Disconnect both welding cables from Pacemaker.
  4. Measure the resistant of both cable to earth. If the value is very low maybe the transformer primary side have short circuit to earth or the cables are damaged and make some contact to earth. If it looks ok (endless or very high resistant) go to point 5.
  5. Take the welding copper wire completely out of welder.
  6. Control that pendulum roller head is lift up. Put a carton or another insulating material between both welding rollers to make sure that you don’t have any contact between the rollers.
  7. Connect an external cable 230VAC (phase and neutral) to the welding cables, which you have removed on pacemaker before. Use for this external supply a 10A fuse breaker to protect the supply in case of a short circuit of welding transformer. (Take a look to picture on point 3)
  8. Before you switch on the external supply check again:
    – Wire removed?
    – Pendelum rollerhead lift up and isolation between welding rollers?
  9. Now switch on the external supply. If the 10A fuse breaker does not trip it is a good sign and it doesn’t look like short circuit of welding transformer.
  10. To control the output of welding transformer you can measure the voltage between the welding rolls (VAC). The measured voltage is depending on the type of welding transformer. If you change the transformer step this value has also to change. Check the output voltage of each step. Don’t worry if you measure only around 5VAC, the output voltage of welding transformer is a low voltage.

Before you change the transformer step switch off first the external supply!!!

 

Download PDF english

Download PDF chinese

  • Check function and the contamination of the ventilators.
    • If necessary clean or change them.

Questions:

Do you have instructions on how to upgrade our current Pacemaker software? Yes.

 

Change of the processor board

The software for the Pacemaker is memorized on a small processor board. For an update with new software you need to change this board.

IMPORTANT:
Before you start to change the board write down all values/parameters (e.g. main current, frequency etc.) for each can you have saved in pacemaker memory.
This not necessary for the CMX1 and X8 welder, because the parameters are safed in the panel.

 

Switch of main switch of pacemaker / machine.

 

WARNING:
Wait 5 minutes before you remove the cover. Capacitors with high voltage inside!

 

Remove the processor board carefully by hand. Do not use any tools for that.

 

Install the new processor board.

 

Be careful about the board position and especially the position of the connectors.

 

NOTE:
Depending on your current Pacemaker version you have to change the MAX IC as well.

 

The MAX IC controls all outputs and IGBT`s and works also with a software.

 

NOTE:
To remove the IC, use the delivered special tool. Never use a screwdriver or another tool. You will destroy the socket!

 

Take MAX IC out with the designated tool.

 

Install the new MAX IC.

 

Double-check the position before you press the IC in the socket!

 

Switch the main switch “ON” and check all parameter (current, frequency, etc.) before you start production.

All Can Man content is now also available on the Soudronic Group website.
Where do you want to continue your journey?
All Can Man content is now also available on the Soudronic Group website.
Where do you want to continue your journey?