Support

12 Support Entries

The motherboard battery is a CR2032 lithium-metal cell. It is used to supply power to the clock integrated on the motherboard. If the battery is depleted or missing, the date and time are displayed incorrectly. Recommendation for replacement interval is 5 years.

For instructions on how to replace the battery use the download link below. You will also find the correct battery type there.

Download instruction

The motherboard battery is a CR2032 lithium-metal cell. It is used to supply power to the clock integrated on the motherboard. If the battery is depleted or missing, the date and time are displayed incorrectly. Recommendation for replacement interval is 5 years.

For instructions on how to replace the battery use the download link below. You will also find the correct battery type there.

Download instruction

All Beckhoff control units are equipped with a UPS to ensure the proper shutdown of the control IPC. However, this only works if the battery is in perfect condition to prevent data loss and ensure the flawless operation of the control system. The battery module for the UPS must be replaced every 5 years.

To order a new battery please contact spares.canman@soudronic.com.

For instructions on how to replace the battery use the download link below. You will also find the correct order number there.

Download instruction

All Beckhoff control units are equipped with a UPS to ensure the proper shutdown of the control IPC. However, this only works if the battery is in perfect condition to prevent data loss and ensure the flawless operation of the control system. The battery module for the UPS must be replaced every 5 years.

To order a new battery please contact spares.canman@soudronic.com.

For instructions on how to replace the battery use the download link below. You will also find the correct order number there.

Download instruction

Problem:

Some Beckhoff i/o terminals are not active and status LEDs are off, control does not respond to commands.

Possible Causes & Resolutions:

  • The 24Vdc supply of the EK1100 coupler or the EL9410 intermediate supply terminal is missing or the voltage is too low > Check all connections, measure voltage, check fuses.
  • Bad contact between the terminals > Switch off the main power and remove the terminals. Clean the contact between the terminals.
  • Defective EL9410 intermediate supply terminal > Exchange terminal.
  • Defective EK1100 coupler > Exchange coupler.

 

 

 

Problem:

After main switch off and on again, HMI piece counter values and settings are lost or old recipes are loaded.

Possible Causes & Resolutions:

  • IPC has not shut down correctly.Check the IPC after you switched off the main switch: Normally it will continue to run for at least 30 seconds to shut down correctly. If LED’s of IPC goes off within a few second, the battery of the UPS – unit is dead and needs to be replaced.

 

Problem:

Drives start but the slitter does not start cutting in automatic mode. Pockets on sheet collector are full but stacks are not pushed out automatically and the button on the panel for pushing out manually does not work either.

Possible Causes & Resolutions:

  • Signal feeder active: Check the signal from feeder. When the feeder pick up the sheet stacks inside collector, the push out of new sheet stacks is blocked.

 

  • Reed switch B267 blank collector closed: If the blank collector is not closed, the function push out sheet stacks does not start. Check reed switch B267.

 

  • Light barrier B266 sheet stack in pick-up position: If this light barrier is damaged or not adjusted well, the function push out sheet stacks does not start.

 

  • Wrong setup for blank collector: If wrong type of blank collector is selected, push out of sheet stacks is disabled.

Problem:

First operation feeds the stripes too early into the upper magnetic belt of 2. table. Therefore the stripes do not stop on the upper magnetic belt and will be ejected through the slot in the frame of the 2. table.

Possible Causes & Resolutions:

Sensor B255: This sensor sends a signal to the control that the upper magnetic belt is ready for new stripes. The sensor might be defect or wrong adjusted.

Sensors B237 and B238: Sensor B237 does slow down the sheets and B238 stops the sheets for the centering. If the sheets do not stop, they may run through the first operation without being centered and with incorrect timing. The sensors might be defect or wrong adjusted.

 

Problem:

  • Speed of the drives changes during production

 

Possible causes & resolutions:

  • Wrong position of the switch for the terminating resistor on the bus plug.
    Check all switches on the complete bus system. Follow the cable thoroughly from first DP bus device (PLC) to last DP bus device. The terminating resistor switch of first and last must be set to „ON”, all other to „OFF“.
  • Bus connector/plug defect
  • Check wiring of all profibus cables, especially the connection of the cable shield inside the plug.
  • Problem of terminating resistor supply by last device on bus. Try to change the profibus wiring to use on another device as last client.

 

An overvoltage suppressor (or surge suppressor) is an appliance designed to protect electrical devices from voltage spikes. A surge suppressor attempts to regulate the voltage supplied to an electric device by either blocking or by shorting to ground voltages above a safe threshold.

These surge suppressors are built in to the latest Pacemaker models and machine controls (from 2009).

Check, if one or more modules of the surge suppressors are red/defect. Replace the red modules.

Attention!!!

Do not bridge the signalling contacts and run the machine with defective red modules because they no longer protect the system from voltage peaks!!!
If the modules are defective, check the main supply. Measure and check all voltages between the phases and all phases to earth before exchange the modules and restart the machine.

Possible causes:

  • No supply of a slave on the bus system.
    • Check supply of all slaves.
      Emergency stop must be released.
  • Address of slave on Profibus is wrongly adjusted.
    • Check setting of all DIP switches on the Lenze bus module and on the Linmot controller.
      You can find the correct setting on the wiring diagram.
  • Wrong position of the switch for end resistant on the bus plug.
    • Check all switches on the complete bus system. Seriously follow the cable from PLC to the last slave. First plug and plug of last slave must be set to ON, all other plugs to OFF.

All Can Man content is now also available on the Soudronic Group website.
Where do you want to continue your journey?
All Can Man content is now also available on the Soudronic Group website.
Where do you want to continue your journey?