Problem:
The HMI cannot be started and the browser shows „NOT FOUND, The requested URL /en/default.htm was not found on this server“.
Possible Causes & Resolutions:
Not connected to Canman Wifi (only for wireless connected iPad’s): Check the wifi settings. Choose Canman wifi and try again.
IPC has not shut down correctly: In this case probably the HMI software can’t start up automatically by restarting the machine.
Check the IPC after you switched off the main switch: Normally it will continue to run for at least 30 seconds to shut down correctly. If LED’s of IPC goes off within a few second, the battery of the UPS – unit is dead and needs to be replaced. Contact Canman for online support to restart HMI.
Problem:
Graph remains grey and shows no curves at all.
Possible Causes & Resolutions:
Avoid very fast switching between pages. This causes overloading of the browser.
Close alle open browser connection (HMI app) and wait for >2 min.
Now you should be able to open the HMI without error message.
Close HMI app on iPads with home button:
Close HMI app on newer iPads without home button:
Note: If you use a new iPad the icons for the machine type can be produced, when you tap on “Add to home screen“ button.
Problem:
Display shows „Could not activate iPad“
Possible causes & resolutions:
For connecting an alternative display / PC, please have a look at the separate FAQ.
Important things to know:
1. Problem:
The graph is not showing any values / no picture at all.
Possible Causes & Resolutions:
2. Problem:
The graph of the G-Sensor does not show a steady graph but shows greater fluctuations (= can gap).
Possible Causes & Resolutions:
Problem:
iPad does not connect to the machine. Screen remains gray and shows no values.
Possible Causes & Resolutions:
Problem:
The decrement counter shows the number of cans between the welding station and first light barrier of the eject station. If the value is wrong, the ejection of cans is out of sync with the faulty products.
Resolution:
Problem:
The decrement counter is not stable, which leads to continuously smaller values during full production.
Possible Causes & Resolutions: