The motherboard battery is a CR2032 lithium-metal cell. It is used to supply power to the clock integrated on the motherboard. If the battery is depleted or missing, the date and time are displayed incorrectly. Recommendation for replacement interval is 5 years.

For instructions on how to replace the battery use the download link below. You will also find the correct battery type there.

Download instruction

The motherboard battery is a CR2032 lithium-metal cell. It is used to supply power to the clock integrated on the motherboard. If the battery is depleted or missing, the date and time are displayed incorrectly. Recommendation for replacement interval is 5 years.

For instructions on how to replace the battery use the download link below. You will also find the correct battery type there.

Download instruction

All Beckhoff control units are equipped with a UPS to ensure the proper shutdown of the control IPC. However, this only works if the battery is in perfect condition to prevent data loss and ensure the flawless operation of the control system. The battery module for the UPS must be replaced every 5 years.

To order a new battery please contact spares.canman@soudronic.com.

For instructions on how to replace the battery use the download link below. You will also find the correct order number there.

Download instruction

All Beckhoff control units are equipped with a UPS to ensure the proper shutdown of the control IPC. However, this only works if the battery is in perfect condition to prevent data loss and ensure the flawless operation of the control system. The battery module for the UPS must be replaced every 5 years.

To order a new battery please contact spares.canman@soudronic.com.

For instructions on how to replace the battery use the download link below. You will also find the correct order number there.

Download instruction

Problem:

Circuit breaker Q5 trips when the machine is switched on or during production.

Possible Causes or Resolutions:

  • Measure voltages at all phases, even under load. It is possible that one phase did drop down, and this triggered the circuit breaker.
  • Measure the current of each phase with a current clamp after Q5. If the measured value is below the value of the circuit breaker and Q5 still keeps tripping, the circuit breaker may be defective. Replace it.
  • Maybe the parameter “Low bat voltage” (coming from Pacemaker) is set too low: That means that the contactor in the Pacemaker closes too early with a precharge voltage that is too low and therefore Q5 trips. To check this, please open a ticket to contact CanMan.

Problem:

All drives are starting correctly, but the vacuum and welding current are not active.

Possible Causes & Resolutions:

  • Welding pressure has been set below the min. value of 2.0 bar => Check the welding pressure setting value on the precise air-regulator and reset if needed.
  • Solenoid valve welding pressure Y10 does not work correctly  => Check the welding pressure valve Y10. Does the valve switch correctly and do the welding rollers close?
  • Welding rollers are closing and welding pressure is set correct, but no welding pressure value is displayed on the HMI => Check whether the analogue sensor B77 is working correctly or not.

 

 

 

 

Problem:

Some Beckhoff i/o terminals are not active and status LEDs are off, control does not respond to commands.

Possible Causes & Resolutions:

  • The 24Vdc supply of the EK1100 coupler or the EL9410 intermediate supply terminal is missing or the voltage is too low > Check all connections, measure voltage, check fuses.
  • Bad contact between the terminals > Switch off the main power and remove the terminals. Clean the contact between the terminals.
  • Defective EL9410 intermediate supply terminal > Exchange terminal.
  • Defective EK1100 coupler > Exchange coupler.

 

 

 

Problem:

After main switch off and on again, HMI piece counter values and settings are lost or old recipes are loaded.

Possible Causes & Resolutions:

  • IPC has not shut down correctly.Check the IPC after you switched off the main switch: Normally it will continue to run for at least 30 seconds to shut down correctly. If LED’s of IPC goes off within a few second, the battery of the UPS – unit is dead and needs to be replaced.

 

Problem:

Machine stops and message „Pacemaker: Profibus communication error“ is displayed.

Possible Causes & Resolutions:

  • Cooling water valve: Wrong type of valve or plug without protective circuit (suppressor). The voltage peaks can cause interferences in the Pacemaker electronics. Always use the original plug and valve type.
  • Profibus plug: On the plug of first and last client of profibus system the termination resistant must be set to ON. Otherwise interference may occur.
  • Profibus cables: Check the position of the cables in the control unit. If they are close to contactors, high voltage peaks can create interferences.

An overvoltage suppressor (or surge suppressor) is an appliance designed to protect electrical devices from voltage spikes. A surge suppressor attempts to regulate the voltage supplied to an electric device by either blocking or by shorting to ground voltages above a safe threshold.

These surge suppressors are built in to the latest Pacemaker models and machine controls (from 2009).

Check, if one or more modules of the surge suppressors are red/defect. Replace the red modules.

Attention!!!

Do not bridge the signalling contacts and run the machine with defective red modules because they no longer protect the system from voltage peaks!!!
If the modules are defective, check the main supply. Measure and check all voltages between the phases and all phases to earth before exchange the modules and restart the machine.