Problem:

Machine stops and message „Pacemaker: Profibus communication error“ is displayed.

Possible Causes & Resolutions:

  • Cooling water valve: Wrong type of valve or plug without protective circuit (suppressor). The voltage peaks can cause interferences in the Pacemaker electronics. Always use the original plug and valve type.
  • Profibus plug: On the plug of first and last client of profibus system the termination resistant must be set to ON. Otherwise interference may occur.
  • Profibus cables: Check the position of the cables in the control unit. If they are close to contactors, high voltage peaks can create interferences.

Click here for the status LED’s of the Beckhoff PC and how to access the PC in case of a trouble shooting.

 

  • If the Led are not switching off after machine power off (wait at least 5min. !), remove the X101 plug on the IPC and plug it back after some seconds.

 

Possible cause:

  • Check first whether the conveyor / elevator unit is blocked somewhere!
  • Check the 24 VDC fuse according electrical diagram. Make sure that the correct size will be used!
  • Check the setting of the respective sensor (according electrical diagram), which allows the conveyor to move if the sensor is active / free!
  • Take the 24 VDC motor out, and check whether the motor is defective or not! Make sure that the conveyor is not moving downwards as soon as the mechanical connection between motor and elevator unit has been released!